Maryland Bids > Bid Detail

H999--VAMHCS Annual Medical Gas Certification Services Base Plus four options

Agency:
Level of Government: Federal
Category:
  • H - Quality Control, Testing, and Inspection Services
Opps ID: NBD00159287499841580
Posted Date: May 25, 2023
Due Date: Jun 14, 2023
Solicitation No: 36C24523Q0677
Source: https://sam.gov/opp/ebce2312d6...
H999--VAMHCS Annual Medical Gas Certification Services Base Plus four options
Active
Contract Opportunity
Notice ID
36C24523Q0677
Related Notice
Department/Ind. Agency
Looking for contract opportunity help?

Procurement Technical Assistance Centers (PTACs) are an official government contracting resource for small businesses. Find your local PTAC (opens in new window) for free government expertise related to contract opportunities.

General Information
  • Contract Opportunity Type: Sources Sought (Original)
  • All Dates/Times are: (UTC-04:00) EASTERN STANDARD TIME, NEW YORK, USA
  • Original Published Date: May 24, 2023 07:51 am EDT
  • Original Response Date: Jun 14, 2023 08:00 am EDT
  • Inactive Policy: Manual
  • Original Inactive Date: Aug 13, 2023
  • Initiative:
Classification
  • Original Set Aside:
  • Product Service Code:
  • NAICS Code:
  • Place of Performance:
    Department of Veterans Affairs VAMC Baltimore , MD 21201
Description
DISCLAIMER
This RFI is issued solely for information and planning purposes only and does not constitute a solicitation. All information received in response to this RFI that is marked as proprietary will be handled accordingly. In accordance with FAR 15.201(e), responses to this notice are not offers and cannot be accepted by the Government to form a binding contract. Responders are solely responsible for all expenses associated with responding to this RFI.
Page 10 of 10

Page 10 of 10
STATEMENT OF WORK
Annual Medical Gas Delivery Systems Testing and Inspection for the VA Maryland Health Care System
October 2023 with 4 option years
SCOPE OF WORK

The Contractor shall provide a certified ASSE 6030 Medical Gas Verifier(s), testing equipment, supplies and transportation. All work to be completed within 120 calendar days from the award date. Contractor to submit a work schedule for each site for the COR for approval. The contractor will perform the inspection and testing of the medical gas delivery systems for the Department of Veterans Affairs, VA Maryland Health Care System at these three locations:

Baltimore VA Medical Center
10 North Greene St.
Baltimore, MD 21201

Loch Raven Medical Center
3900 Loch Raven Blvd
Baltimore, MD 21228
Perry Point VA Medical Center
Perry Point, MD 21902-1000
MEDICAL GAS SYSTEMS FOR EACH SITE

Baltimore VA Medical Center
10 North Greene St,
Baltimore, MD 21201

Master alarm panels (3 ea.)
Master Alarm Signals (54 ea.)
Area Alarm Panel (19 ea.)
Alarm Signals (68 ea.)
Zone Value Boxes (36 ea.)
Zone Values (126 ea.)
Outlets (1,462 ea.) O2, MA, N2O, N2, VAC, WAGD
Bulk O2 with reserve tank, supplier/owner Air Products
Medical Air System 7th floor (3 ea.) 15-hp oil-less compressors
Dental Air System, room 1D-166, POWEREX (460v/3ph)
Dental Vacuum System, room 1D-166, ECO VAC, duplex 7.5hp
Dental Nitrogen manifold system (2 ea.) left side and (2 ea.) right side
Medical Vacuum System 7th floor (3 ea.) 15-hp oil-lubed rotary
Nitrogen manifold system (8 ea.) bottles left side and (8 ea.) bottles right side
Nitrous oxide manifold system (8 ea.) bottles left side and (8 ea.) bottles right side
Loch Raven VA Medical Center
3900 Loch Raven Blvd
Baltimore, MD 21228

Master alarm panels (2 ea.)
Master Alarm Signals (24 ea.)
Area Alarm Panel (4 ea.)
Alarm Signals (12 ea.)
Zone Value Boxes (4 ea.)
Zone Values (12 ea.)
Outlets (240 ea.) O2, MA, VAC
Bulk O2 with reserve bottles, supplier/owner Air Products
Medical Air System duplex 5-hp oil-less compressors
Medical Vacuum System (2 ea.) 5-hp oil-lubed rotary

Perry Point VA Medical Center
Perry Point, MD 21902

Master alarm panels (total: 6 ea.)
Building 23H (2 ea.)
Building 19H (1 ea.)
Building 14H (2 ea.)
Building 361 (1 ea.)

Master Alarm Signals (98 ea.)
Area Alarm Panel (10 ea.)
Alarm Signals (98 ea.)
Zone Value Boxes (26 ea.)
Zone Values (70 ea.)
Outlets (263 ea.) O2, MA, VAC
Bulk O2 & reserve tank location 14H supplier/owner is Airgas (Air Liquide)
Bulk O2 & reserve tank location 19H supplier/owner is Airgas (Air Liquide)
Medical Air System location 14H, duplex 5-hp oil-less compressors
Medical Air System location 23H, duplex 5-hp oil-less compressors
Medical Vacuum System location 14H ,duplex 5-hp oil-lubed rotary
Medical Vacuum System location 23H ,duplex 5-hp oil-lubed rotary
Medical Vacuum System location 19H ,duplex 5-hp oil-lubed rotary
Medical Vacuum System location 24H ,duplex 1-hp oil-lubed rotary
Dental Air and Dental Vacuum

SPECIFICATIONS:

The Contractor shall inspect and certify the medical gas delivery systems at each site in accordance with most recent NFPA-99 Health Care Facilities, NFPA-55 Compressed Gases and Cryogenic Fluids, and NFPA-70 National Electrical Code.
Â

Testing Master Alarm Panels
Function test of all signals from source and bulk systems to master alarm panels. Simulate failures at all source field switches. Includes determination of trip setting accuracy and correct bulk/source system labeling.
Â
Testing Area Alarm Panels
Tests all audible and visual alarm signals for continuity, determine accuracy of trip settings and readouts. Includes determination of proper area served signage. Pressure transducers/pressure switches will be function tested to determine proper operation of hi/lo pressure signals, proper communication with area panel, and determination of hi/lo trip setting on alarm display.
Â
Zone valves
Verify proper area served labeling, test for external leakage and validate accuracy of pressure gauge. Particulate samples are taken in each zone to test for contamination.
Â
Bulk Oxygen Supply Systems
Test operation of the reserve and reserve in use signaling devices, check proper function of level activating switch. Inspect all cryogenic tanks for security, leaks, control configuration and labeling. Inspect Emergency Oxygen Supply Connection (EOSC).

Gas Manifold Source Systems
Leak test all manifold components including valves, pigtails, and regulators. Test for proper reserve in use pressure switch activation. Test for proper operation of the changeover for secondary supply.
Â
Medical Air System
Verify compressor operating within manufacturer specifications. Check for documented maintenance plan in place. Function test of automatic alternating controls. Test audible and visual alarms. Test pressure across filters. Calibrate dew point monitor and verify proper operation.
Â
Medical Vacuum System
Verify maintenance conducted according to manufacturer specifications. Function test automatic alternating controls. Test pressure/vacuum switch for proper operation. Validate frequency of pump starts and duration of runs. Measure cut-in and cut-out pressure/vacuum.

Medical Gas Outlets
Vacuum inlets and pressure gas outlets. Test flow of all vacuum inlets. Check pressure and flow of all outlets: patient care areas, emergency rooms, intensive care, procedure labs, operating rooms and recovery rooms. The surgical rooms testing is performed after-hours. This testing includes coordination with the Baltimore site POC.

Manufactured Assemblies
Verify that each joint and DISS fitting is examined for leakage and that the flexible
assemblies are in a safe working condition.
WORK SCHEDULE:
Normal Working Hours. Normal working hours are from 7:00 am to 4:30 pm, Monday through Friday, except federal holidays.

The contractor shall try to minimize the interruption of patient care areas while checking the medical gas outlets. The contractor shall check-in with the nurse manager for each Nursing Unit before starting.

NOTE At the Baltimore Medical Center there are (9-ea) operating rooms, recovery rooms and same day surgeries rooms which will to be completed off hours. Only the Baltimore site has operating rooms, recovery rooms and same day surgeries.

Second Visit required for the Baltimore Site Only: A second visit is required to capture the AOV outlets that were being used during the 1st inspection. Second visit for these areas: SICU, MICU, CICU, and ER If the AOV outlet is still being used on 2nd visit then just noted unable to check, document the location and outlet and state why.

BRIEFING on final report. Contractor shall provide a 1-hour briefing on all three sites which covers Deficiencies e, findings and recommendations. The briefing will be held at the Perry Point site. This is to be scheduled within 10-days after the final reports are submitted to the VA.
IV. CONTRACTOR PERSONNEL

A. Personnel Experience. All work shall be performed by competent technicians, experienced and qualified to perform inspection and certification on the equipment listed in this contract. Technicians used to perform the work shall be NFPA-99 trained and be current with the ASSE 6030 Medical Gas Verifier certification for healthcare facilities.

Prior to beginning performance, Contractor shall submit to the Contracting Officer, copies of certifications and a list of credentials for all technicians that will perform contract work. Contractor must also provide a list of three (3) reference contacts that have been provided medical gas certification for similar medical facilities. The VA reserves the right to reject any of the contractor s personnel and refuse them permission to work on VA equipment.

B. Conduct of Personnel. The Contractor shall ensure that his/her personnel present a professional appearance always and that their conduct shall not reflect discredit upon this facility or the Department of Veterans Affairs. The Contractor shall remove from the job site any employee for reasons of misconduct or security. The removal from the job site of such a person shall not relieve the Contractor of the requirement to provide sufficient personnel to perform adequate and timely service. All employees shall be legal residents of the United States and be able to understand, speak, read, and write the English language.

C. Identification of Employees. Contractor's employees shall conspicuously display on their person a badge provided by the Contractor that shall include the full name of the employee, the name under which the Contractor is doing business and a badge serial number.

VI. CONTRACTOR QUALITY CONTROL
The Contractor shall establish and maintain a Quality Control Program that ensures that all requirements of the contract are provided as specified.

VII. ACCEPTANCE
Upon completion of the inspections, the Contractor shall submit a typed inspection report for each site. Provide (1) hard copy bonded and mail copies to COR. Provide (1) electronic copy to COR.

The Inspection Report shall include:
Table of contents
Current Inventory
Master Alarms
Zone Values
Outlets
Gaseous Contaminants
Medical Air Dew Point Temperatures
Solid Particulate Contaminants (0.45 um filters)
Oxygen Bulk Source liquid
Medical Air Bulk source
Nitrous Oxide Bulk Source
Nitrogen Oxide Bulk Source
Vacuum Sources
Findings, Deficiencies and Recommendations.
Final acceptance of services performed will be made by the Government upon receipt of these documents. Contractor shall schedule a 1-hour zoom call to brief the M&O engineering staff on the Findings, Deficiencies and Recommendations for all three sites.

VIII. SMOKING POLICY
Smoking is prohibited.


Attachments/Links
Contact Information
Primary Point of Contact
Secondary Point of Contact


History
  • May 24, 2023 07:51 am EDTSources Sought (Original)

TRY FOR FREE

Not a USAOPPS Member Yet?

Get unlimited access to thousands of active local, state and federal government bids and awards in All 50 States.

Start Free Trial Today >